Ameren Fast Tracks 345-kV Repairs

机译:Ameren快速通道345 kV维修

获取原文
获取原文并翻译 | 示例
           

摘要

A quick fix overcomes a bus duct failure and keeps the power flowing until the new cable circuit is installed. THREE YEARS AFTER INHERITING A 30-YEAR-OLD 345-KV SF{sub}6 BUS DUCT installed on a critical transmission line, Ameren Corp. (St. Louis, Missouri, U.S.) engineers faced significant repair challenges. Approximately 1100 ft (335 m) of bus duct has operated in the middle of a 30-mile (48-km) line that runs from the Duck Creek power plant to the Tazewell substation in central Illinois, U.S. Critical to the Ameren system, this line provides stability to the Peoria, Illinois, area and is one of two outlets for Duck Creek. Although the bus duct is located at the Edwards plant, the line does not connect to the plant, it simply passes through the switchyard. Aware this bus duct was nearing the end of its useful life, Ameren was in the process of evaluating replacement options when, on June 22, 2006, the 1100-ft section of 345-kV bus duct failed as a result of a lightning strike on the overhead line.
机译:快速修复可以克服母线管故障,并保持电源畅通,直到安装了新的电缆电路。 Ameren Corp.(美国密苏里州圣路易斯)的工程师在将30年的345 KV SF {sub} 6 BUS DUCT植入关键传输线上后三年,工程师面临着重大的维修挑战。从Duck Creek电厂到美国伊利诺伊州中部的Tazewell变电站,到Ameren系统,这条长达30英里(48公里)的线路中间大约运行着1100英尺(335 m)。这条线为伊利诺伊州皮奥里亚(Peoria)地区提供了稳定性,是鸭溪(Duck Creek)的两个出口之一。尽管母线管位于爱德华兹工厂,但该线路未连接至工厂,只是通过配电站。意识到该母线槽已接近使用寿命,2006年6月22日,在345 kV母线槽中1100英尺长的部分由于雷击而失败,Ameren正在评估替换方案。架空线。