首页> 外文期刊>Solar Energy >Theoretical and testing performance of an innovative indirect evaporative chiller
【24h】

Theoretical and testing performance of an innovative indirect evaporative chiller

机译:创新的间接蒸发式冷却器的理论和测试性能

获取原文
获取原文并翻译 | 示例
           

摘要

An indirect evaporative chiller is a device used to produce chilled water at a temperature between the wet bulb temperature and dew point of the outdoor air, which can be used in building HVAC systems. This article presents a theoretical analysis and practical performance of an innovative indirect evaporative chiller. First, the process of the indirect evaporative chiller is introduced; then, the matching characteristics of the process are presented and analyzed. It can be shown that the process that produces cold water by using dry air is a nearly-reversible process, so the ideal produced chilled water temperature of the indirect evaporative chiller can be set close to the dew point temperature of the chiller's inlet air. After the indirect evaporative chiller was designed, simulations were done to analyze the output water temperature, the cooling efficiency relative to the inlet dew point temperature, and the COP that the chiller can performance. The first installation of the indirect evaporative chiller of this kind has been run for 5 years in a building in the city of Shihezi. The tested output water temperature of the chiller is around 14-20 ℃, which is just in between of the outdoor wet bulb temperature and dew point. The tested COP_(r,s) of the developed indirect evaporative chiller reaches 9.1. Compared with ordinary air conditioning systems, the indirect evaporative chiller can save more than 40% in energy consumption due to the fact that the only energy consumed is from pumps and fans. An added bonus is that the indirect evaporative chiller uses no CFCs that pollute to the aerosphere. The tested internal parameters, such as the water-air flow rate ratio and heat transfer area for each heat transfer process inside the chiller, were analyzed and compared with designed values. The tested indoor air conditions, with a room temperature of 23-27 ℃ and relative humidity of 50-70%, proved that the developed practical indirect evaporative chiller successfully satisfy the indoor air conditioning load for the demo building. The indirect evaporative chiller has a potentially wide application in dry regions, especially for large scale commercial buildings. Finally, this paper presented the geographic regions suitable for the technology worldwide.
机译:间接蒸发式冷却器是一种用于在湿球温度和室外空气露点之间的温度下产生冷却水的设备,该设备可用于建筑HVAC系统。本文介绍了一种创新的间接蒸发式冷却器的理论分析和实际性能。首先介绍了间接蒸发式冷却器的过程;然后,提出并分析了该过程的匹配特性。可以证明,使用干燥空气生产冷水的过程几乎是可逆的,因此间接蒸发式冷水机组的理想生产冷水温度可以设置为接近冷水机进口空气的露点温度。设计了间接蒸发式冷水机组后,进行了仿真分析,以分析输出水温,相对于进口露点温度的冷却效率以及冷水机组的性能系数。这种间接蒸发式制冷机的第一台设备已经在石河子市的一座建筑中运行了5年。测试的冷水机出水温度约为14-20℃,介于室外湿球温度和露点之间。研发的间接蒸发式冷却器的测试COP_(r,s)达到9.1。与普通的空调系统相比,间接蒸发式冷却器可节省40%以上的能耗,原因是能耗仅来自泵和风扇。额外的好处是,间接蒸发式冷却器不使用会污染大气层的氟氯化碳。分析冷却器内部每个传热过程的测试内部参数,例如水-空气流速比和传热面积,并将其与设计值进行比较。在室温为23-27℃,相对湿度为50-70%的室内空气条件下进行的测试证明,所开发的实用间接蒸发式制冷机成功地满足了演示建筑的室内空调负荷。间接蒸发式冷水机在干旱地区具有潜在的广泛应用,特别是对于大型商业建筑。最后,本文介绍了适用于全球技术的地理区域。

著录项

  • 来源
    《Solar Energy》 |2010年第12期|p.2041-2055|共15页
  • 作者

    Yi Jiang; Xiaoyun Xie;

  • 作者单位

    Department of Building Science and Technology, Tsinghua University, Beijing 100084, China;

    Department of Building Science and Technology, Tsinghua University, Beijing 100084, China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);美国《生物学医学文摘》(MEDLINE);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    indirect evaporative chiller; evaporative cooling; dry air; dew point temperature;

    机译:间接蒸发式冷却器蒸发冷却;干燥的空气;露点温度;