首页> 外文期刊>Russian electrical engineering >Modeling the saturation processes of a power-transformer core under simultaneous direct and alternating current passing through the winding
【24h】

Modeling the saturation processes of a power-transformer core under simultaneous direct and alternating current passing through the winding

机译:在直流电和交流电同时通过绕组的情况下对电力变压器铁心的饱和过程进行建模

获取原文
获取原文并翻译 | 示例
           

摘要

A mathematical model of a three-phase two-winding step-up power transformer with the winding circuit Δ/Yo with simultaneous ac and dc currents passed through the grounded winding has been developed. The proposed model is represented by a system of differential equations, which are nonlinear because of the nonlinearity of the inductive resistances of the magnetization curve. The calculation results for a TDTs-400000/242/20 shell-core transformer are given. The model takes into account the effect of dc on the saturation of the power-transformer core, which is especially important under asymmetrical modes that can occur during thunderstorms, seismic activities, or space-weather disturbances.
机译:建立了三相两绕组升压型电力变压器的数学模型,其绕组电路Δ/ Yo同时有交流和直流电流通过接地绕组。所提出的模型由微分方程组表示,由于磁化曲线的感应电阻是非线性的,所以它们是非线性的。给出了TDTs-400000 / 242/20壳式铁心变压器的计算结果。该模型考虑了直流对电力变压器铁心饱和的影响,这在雷暴,地震活动或空间天气干扰期间可能发生的非对称模式下尤其重要。