首页> 外文期刊>日本建築学会環境系論文集 >居住者の温冷感を考慮した空調負荷計算法に関する研究: 間欠空調における予熱予冷負荷の発生性状および過大な予熱予冷負荷への対策
【24h】

居住者の温冷感を考慮した空調負荷計算法に関する研究: 間欠空調における予熱予冷負荷の発生性状および過大な予熱予冷負荷への対策

机译:考虑住户热感的空调负荷计算方法研究:间歇式空调中预热预冷负荷的产生及对策

获取原文
获取原文并翻译 | 示例
           

摘要

Currently, the air-conditioning load is calculated for transmission thermal energy from the wall surfaces to indoor air because the air-conditioning load is defined for the thermal energy that it should supply indoor air with to keep a fixed room temperature. The air-conditioning load calculated in this way becomes the function of the room temperature set point and is unrelated to thermal sensation of the resident. This paper suggested a new load calculation method which considered thermal sensation of the resident based on a point of view of comfort air conditioning. By this new load calculation method, the load is calculated for thermal energy to remove by the room to keep PMV of the indoor specific place a set point. However, in intermittent air-conditioning system, the load occurs greatly to control PMV in a set point in a short time. This paper is aimed at examining the effectiveness of the new load calculation method in intermittent air-conditioning system.%1.はじめに現在、空調負荷は、室温を一定に保つために室内空気に供給すべき熱量として定義されているため、一定の室温が維持されたときに壁体などから室内空気への伝達熱量として計算されている。このような空調負荷計算法(以下、「現行法」)で求めた負荷は、室温設定値の関数となる。それに基づいて設計された空調システムでは、負荷計算の段階で十分に考慮されていない居住者の温冷感は竣工後の運用段階で制御系などを援用して、快適性などの不明部分を調整しているのが現状である。
机译:当前,计算空调负荷是为了将热能从壁表面传递到室内空气,因为空调负荷是为保持室内温度固定而应向室内供给的热能定义的。以这种方式计算出的空调负荷成为室温设定点的函数,并且与居民的热感无关。本文提出了一种新的负荷计算方法,该方法基于舒适空调的角度考虑了居民的热感。通过这种新的负荷计算方法,可以计算出为消除室内热能而将室内特定场所的PMV保持在设定点的负荷。但是,在间歇式空调系统中,为了在短时间内将PMV控制在设定点而产生很大的负荷。本文旨在研究这种新的负荷计算方法在间歇式空调系统中的有效性。%1。こ,一定の室内が维持されたときに壁体に室内空気への伝达转化として计算されている。このような空调负荷计算法(以下,「现行法」)で求めた负荷は,室内设定値の关数とて。の不明部分を调整しているのが现状である。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号