摘要

This paper describes a new control approach for secure fault-ride through of wind farms connected to the grid through a voltage source converter-based high voltage DC transmission. On fault occurrence in the high voltage grid, the proposed control initiates a controlled voltage drop in the wind farm grid to achieve a fast power reduction. In this way overvoltages in the DC transmission link can be avoided. It uses controlled demagnetization to achieve a fast voltage reduction without producing the typical generator short circuit currents and the related electrical and mechanical stress to the wind turbines and the converter. The method is compared to other recent FRT methods for HVDC systems and its superior performance is demonstrated by simulation results.
机译:本文介绍了一种新的控制方法,用于通过基于电压源转换器的高压直流输电连接到电网的风电场实现安全的故障穿越。在高压电网中发生故障时,建议的控制会在风电场电网中启动受控的压降,以实现快速的功率降低。这样,可以避免直流传输链路中的过电压。它使用受控的退磁来实现快速的电压降低,而不会产生典型的发电机短路电流以及对风力涡轮机和变流器产生的相关电气和机械应力。将该方法与用于HVDC系统的其他最新FRT方法进行了比较,并通过仿真结果证明了其优越的性能。