Analyses indicate that significant differences can exist between effective probability of flashovers (PFOs) for a given insulation level, depending on whether surge arresters or circuit-breaker closing resistors are used to hold surges to about the same phase-to-ground levels. For phase-to-phase insulation, arresters are significantly less effective than circuit-breaker closing resistors at reducing PFOs. This is true for application of phase-to-ground arresters with or without phase-to-phase arresters. For phase-to-ground insulation, resistors are also more effective than arresters at reducing insulation requirements. This result is particularly applicable for station and line uprating and compact designs. Calculation techniques which consider phase-to-ground surges on all three phases, rather than techniques which simple consider only the phase which has the maximum surge, yield PFOs which more correctly represent the overall PFO of the insulation system.
机译:分析表明,对于给定的绝缘等级,有效击穿概率(PFO)之间可能存在显着差异,具体取决于是否使用电涌放电器或断路器合闸电阻将电涌保持在大约相同的地线水平。对于相间绝缘,在降低PFO方面,避雷器的效率明显低于断路器的闭合电阻。对于具有或不具有相间避雷器的相接地避雷器的应用都是如此。对于相接地绝缘,电阻器在降低绝缘要求方面也比避雷器更有效。该结果特别适用于站和线路升级以及紧凑型设计。计算技术考虑了所有三相的地对地电涌,而不是简单地仅考虑具有最大电涌的相的技术,所产生的PFO更能正确地代表绝缘系统的整体PFO。