首页> 外文期刊>IEEE Transactions on Power Delivery >Survey of failure of surge protective capacitors and arresters on AC rotating machines report by working group 3.4.9 of surge protective devices committee
【24h】

Survey of failure of surge protective capacitors and arresters on AC rotating machines report by working group 3.4.9 of surge protective devices committee

机译:交流电旋转设备中的电涌保护电容器和避雷器的故障调查由电涌保护设备委员会的3.4.9工作组报告

获取原文
获取原文并翻译 | 示例
           

摘要

A survey of manufactures and users of surge protective capacitors and arresters for rotating machines was conducted to obtain device failure data or comparison with failure statistics on rotating machine insulation. Answers to two questions were sought. These questions are: (1) do protective devices reduce or increase the overall machine feature rate; and (2) is there a cost of service benefit derived from application of surge protective devices to rotating machines? The conclusions drawn from this survey are: (1) the service data for machine surge-protective capacitors and arresters are sparse and not usually recorded, and there is little assurance that the data sample was not biased by the absence of records for either a surviving unfailed population or a failed population; (2) it is not a common practice among electric utilities to apply surge-protective devices to AC motors; (3) in utility, industrial, and commercial service, the reliability level of machine-protective surge capacitors was about equal to the average reliability of large motor windings to voltage stress; and (4) if surge protective capacitor application were able to prevent all nonoverheating insulation failures, the overall machine forced outage rate would be changed by only a little.
机译:对旋转机械的电涌保护电容器和避雷器的制造商和用户进行了调查,以获取设备故障数据或与旋转机械绝缘故障统计数据进行比较。寻求两个问题的答案。这些问题是:(1)保护装置是否降低或提高了机器的整体特征率? (2)将电涌保护装置应用于旋转机械是否可带来服务成本收益?从该调查得出的结论是:(1)机器电涌保护电容器和避雷器的服务数据稀疏并且通常不记录,并且几乎不能保证数据样本不会因没有幸存的记录而有偏差。未失败的人口或失败的人口; (2)在电业中,将浪涌保护装置应用于交流电动机不是普遍的做法; (3)在公用事业,工业和商业服务中,机器保护浪涌电容器的可靠性等级大约等于大型电动机绕组对电压应力的平均可靠性; (4)如果使用电涌保护电容器能够防止所有非过热绝缘故障,则整个机器的强制停机率仅会发生很小的变化。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号