首页> 外文期刊>IEEE Transactions on Power Delivery >Comparative analysis of expulsion and current-limiting fuse operation in distribution systems for improved power quality and protection
【24h】

Comparative analysis of expulsion and current-limiting fuse operation in distribution systems for improved power quality and protection

机译:配电系统中放电和限流熔断器运行的比较分析,以改善电能质量和保护

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents a comparative analysis of the effects of expulsion and current-limiting fuse (CLF) operations in distribution systems on power quality and power system protection. This analysis included field tests of both types of fuses on a distribution system in Florida, USA. To further analyze fuse effects on the voltage dip duration and spread of the overvoltages created during the fuse operations throughout the power system, computer simulations were also performed. Unique digital fuse models were developed for use with the EMTP/ATP program. This paper shows that CLFs improve power quality by supporting power system voltage during faults, reducing the voltage dip duration, and do not affect load operation. Additionally, CLFs reduce the fault let-through I/sup 2/t.
机译:本文对配电系统中的放电和限流熔断器(CLF)操作对电能质量和电力系统保护的影响进行了比较分析。该分析包括在美国佛罗里达州的配电系统上对两种类型的保险丝进行的现场测试。为了进一步分析保险丝对电压跌落持续时间的影响以及整个电源系统在保险丝运行过程中产生的过电压的分布,还进行了计算机仿真。开发了与EMTP / ATP程序一起使用的独特数字保险丝模型。本文表明,CLF通过在故障期间支持电力系统电压,减少电压骤降持续时间并且不影响负载运行来改善电能质量。此外,CLF降低了故障通过I / sup 2 / t。