Computation of Ground Resistances and Assessment of Ground Grid Safety at 161/23.9-kV Indoor-Type Substation

机译:161 / 23.9kV室内型变电站的接地电阻计算和接地网安全评估

获取原文
获取原文并翻译 | 示例
           

摘要

This paper computes ground resistances and assesses ground grid safety at three 161/23.9-kV indoor-type substations in the system of the Taiwan Power Company. For computing the ground resistance, a method based on two kinds of two-layer models (i.e., grid buried in the lower-layer of two-layer soil, two-layer soil simplified with one-layer structure of the Sverak's and empirical equations) is used and compared with the method proposed by the one-layer model of the Schwarz's equation in IEEE Standard 80, 2000 edition. As a result, the ground resistance obtained by the two-layer soil simplified with one-layer structure of the empirical equation is near the measurement. For assessing the ground grid safety, the ground potential rise is computed based on the calculated ground resistance and is compared with the minimum touch voltage. As a result, the design of the ground grid at all three 161/23.9-kV indoor-type substations is unsafe under a one-layer model of the Schwarz's equation for humans with 50-kg body weight.
机译:本文计算了台湾电力公司系统中的三个161 / 23.9-kV室内型变电站的接地电阻并评估了接地网的安全性。为了计算接地电阻,一种基于两种两层模型的方法(即,将网格埋在两层土壤的下层中,将两层土壤简化为具有Sverak的一层结构和经验方程式)并与IEEE标准80,2000版中的Schwarz方程的单层模型提出的方法进行了比较。结果,用经验方程式的单层结构简化的两层土壤获得的接地电阻接近测量值。为了评估接地网的安全性,基于计算出的接地电阻计算接地电位上升,并将其与最小接触电压进行比较。结果,在Schwarz方程的单层模型中,对于体重为50公斤的人,在所有三个161 / 23.9-kV室内型变电站中,接地网的设计都是不安全的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号