Modeling of UHV and Double-Circuit EHV Transmission-Line Exposure to Direct Lightning Strikes

机译:超高压和双回路超高压输电线路直接雷击的建模

获取原文
获取原文并翻译 | 示例
           

摘要

This paper comprises the first systematic investigation into the factors that render ultra-high voltage and double-circuit extremely high voltage transmission lines more vulnerable to direct lightning strikes by shielding failure. Such lines are typically characterized by one or more of the following features: massive conductor bundles, extreme conductor heights, and exceptionally high operating voltage. The model addresses the effects of the upward connecting leader onset of conductor proximity, ground field due to cloud charges prior to negative leader descent, positive space-charge generation at ground wires, as well as the operating voltage during the positive half cycle. It has been found that such factors have significant effects on the lateral attractive distance of both conductor bundles and ground wires. An agreement between model findings and field experience is found to be generally satisfactory.
机译:本文包括对导致超高压和双回路极高压输电线路更容易受到屏蔽故障直接雷击影响的因素的系统研究。此类线路通常具有以下一项或多项特征:庞大的导体束,极高的导体高度和极高的工作电压。该模型解决了导体邻近连接的向上引导引线起点,负引线下降之前因云电荷而引起的接地场,在接地线处产生正空间电荷以及正半周期内的工作电压的影响。已经发现,这些因素对导体束和接地线的侧向吸引距离具有显着影响。发现模型结果和现场经验之间的协议通常是令人满意的。