Ground relay protection for transmission systems

机译:传输系统的接地继电器保护

获取原文
获取原文并翻译 | 示例
           

摘要

The relay problems of an electric power system are most important, and are very vital to the successful operation of the system. More and more consideration is being given to the relay engineers' point of view with resultant improvement in system operation. Several large, successful companies undertake no project having any bearing on the primary electric system without due regard to the relay engineer's recommendation. With the transmission networks becoming more and more interconnected, and with the injection into the problem the interconnections with other power companies, the absolute necessity of isolating a faulty line, (or a faulty piece of equipment), is essential and is becoming more clearly recognized by all large companies. Since this article was written, other 66-kv., ground relay tests have been made with a resistor grounded neutral and with a solidly grounded neutral, and some very interesting and unexpected points were discovered. It is hoped these points will be brought out during the discussion of this paper
机译:电力系统的继电问题是最重要的,对系统的成功运行至关重要。继电器工程师的观点越来越受到重视,从而改善了系统的运行。在没有适当考虑继电器工程师的建议的情况下,几家成功的大型公司不会进行任何与主电气系统有任何关系的项目。随着传输网络的互连越来越紧密,以及与其他电力公司的互连问题的出现,隔离故障线路(或设备故障)的绝对必要性是必不可少的,并且越来越清楚地认识到所有大公司。自从撰写本文以来,已经使用中性点接地电阻和中性点牢固接地进行了其他66 kV接地继电器测试,并且发现了一些非常有趣和意想不到的点。希望在本文的讨论中能提出这些观点