首页> 外文期刊>Journal of Fire Sciences >Experimental Study on the Mitigation of Backdraft in Compartment Fires with Water Mist
【24h】

Experimental Study on the Mitigation of Backdraft in Compartment Fires with Water Mist

机译:细水雾缓解隔舱火灾回风的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

In this paper, the results of a reduced-scale experimental test series using water mist to mitigate backdraft in compartment fires are presented. This reduced-scale compartment (1.2m x 0.6m x 0.6m) was fitted with a variety of end opening geometries: middle-slot, upside-slot, downside-slot, door, window and vertical middle-slot, and ceiling opening geometries: slot and window. Water mist was generated by a downward-directed pressure nozzle that was operated at pressure of 0.2 MPa. Experimental variables included fuel flow rate, burn time, water mist injection time and mass, and opening geometries. Histories recorded prior to backdraft included upper layer temperatures, lower layer temperatures, and species concentration for oxygen, carbon dioxide and carbon monoxide. Data collected to quantify the backdraft included opening gas flow velocities and compartment pressures. The experimental results show that water mist is an effective mitigating tactic that is able to suppress backdraft in compartment fires primarily by means of diluting the gas in the compartment and reducing total hydrocarbons mass fraction, rather than by a thermal mechanism of cooling.
机译:在本文中,提出了使用水雾减轻舱室火灾中的回风的小规模实验测试系列的结果。这个缩小的隔间(1.2mx 0.6mx 0.6m)配备了多种端部开口几何形状:中缝,上缝,下缝,门,窗和垂直中缝,以及天花板开口几何:缝和窗口。向下的压力喷嘴在0.2 MPa的压力下产生水雾。实验变量包括燃料流速,燃烧时间,水雾喷射时间和质量以及开孔几何形状。在回溯之前记录的历史记录包括上层温度,下层温度以及氧气,二氧化碳和一氧化碳的物质浓度。收集的用于量化回风的数据包括打开的气流速度和隔室压力。实验结果表明,水雾是一种有效的缓解策略,该方法能够主要通过稀释舱室内的气体并减少总碳氢化合物的质量分数,而不是通过冷却的热机制来抑制舱室火灾中的逆流。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号