首页> 外文期刊>European Transactions on Electrical Power >Two steps numerical method for calculating the AC interference from a faulty power line on nearby buried pipelines
【24h】

Two steps numerical method for calculating the AC interference from a faulty power line on nearby buried pipelines

机译:计算附近地下管道中故障电线的交流干扰的两步数值方法

获取原文
获取原文并翻译 | 示例
           

摘要

The paper presents a numerical method for evaluating induced voltages and currents, at power frequency, onna buried pipeline due to inductive and conductive coupling with a power line in fault condition; both thensystems can have generic layouts represented by broken lines. The algorithm consists of a two steps solutionnof a two wires transmission line model applied at first to the circuit shield wire(s) with earth return and thennto the circuit pipeline with earth return. This calculation method is particularly tailored for industrial and realncases applications. Copyright # 2010 John Wiley & Sons, Ltd.
机译:本文提出了一种数值方法,用于评估在故障情况下与电源线的电感和导电耦合在地下管道上在工频下感应电压和电流的频率。这两个系统都可以具有以虚线表示的通用布局。该算法由两线传输线模型的两步解决方案组成,该模型首先应用于具有接地回路的电路屏蔽线,然后应用于具有接地回路的电路管线。该计算方法特别适合于工业和房地产应用。版权所有©2010 John Wiley&Sons,Ltd.