A new ground impedance measuring element for digital distance relaying of long parallel lines in high fault resistance conditions

机译:一种新的接地阻抗测量元件,用于在高故障电阻条件下进行长距离平行线路的数字距离中继

获取原文
获取原文并翻译 | 示例
           

摘要

Ground impedance measuring elements (ground elements), which are responsible for removing singlephase-to-ground faults in distance relays, are highly prone to underreach when facing a significant resistancernin the fault path. This paper proposes a new ground element with ensured dependability in high fault resistance conditions for the first-zone digital distance relaying of parallel lines. The proposed ground elementrnfunctions on the basis of the fault distance and fault resistance it estimates, online during the faults, throughrnthe equation derived from the voltages and currents of the distributed-parameters line model. Hence, it willrnbe particularly applicable to the parallel lines of long length in which the distributed parameters effect isrnsignificant. The proposed element requires only the data acquired at the relaying location. Further, its function is independent of the structural configuration of the system. Unlike conventional ground elements, thernproposed element preserves its security in case of irrelevant-circuit as well as external faults. Simulationrnstudies conducted in MATLAB and PSCAD/EMTDC examine the proposed ground element in a varietyrnof influencing situations, and the results reveal that it accurately trips the faults in thefirst zone with nornincidence of underreach in case of high resistance faults. The accuracy of the proposed element is overrn99.4% and its tripping time within 0.3–1.3 cycles.
机译:接地阻抗测量元件(接地元件),用于消除距离继电器中的单相接地故障,当面对故障路径中的显着电阻时,极容易发生欠触。本文提出了一种新的接地元件,可在高抗故障条件下确保可靠性,用于并行线路的第一区域数字距离中继。所提出的接地元件根据故障距离和故障电阻在故障期间在线估计,通过从分布参数线模型的电压和电流得出的方程进行估算。因此,它将特别适用于长的平行线,其中分布参数的影响不显着。所提出的元素仅需要在中继位置处获取的数据。此外,其功能独立于系统的结构配置。与传统的接地元件不同,提出的元件可在电路无关以及外部故障的情况下保持其安全性。在MATLAB和PSCAD / EMTDC中进行的仿真研究在各种影响情况下检查了所提出的接地元件,结果表明,在发生高电阻故障的情况下,它准确地使第一区域的故障跳闸,而未达到欠触及。所提出的元件的精度超过99.4%,其跳闸时间在0.3-1.3个周期内。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号