Effects of outer tube length on saturated pool boiling heat transfer in a vertical annulus with closed bottoms

机译:外管长度对底部封闭的垂直环空中饱和池沸腾传热的影响

获取原文
获取原文并翻译 | 示例
           

摘要

To improve pool boiling heat transfer in an annulus with closed bottoms, the length of an outer tube has been changed between 0.2 m and 0.6 m. For the test, a heated tube of 19.1 mm diameter and water at atmospheric pressure has been used. To elucidate effects of the outer tube length on heat transfer results of the annulus are compared with the data of a single unrestricted tube. The change in the outer tube length results in much variation in heat transfer coefficients. As the outer tube length is 0.2 m the deterioration point of heat transfer coefficients gets moved up to the higher heat fluxes because of the decrease in the intensity of bubble coalescence.
机译:为了改善底部封闭的环形空间中的池沸腾传热,外管的长度已在0.2 m至0.6 m之间变化。为了进行测试,使用了直径为19.1 mm的加热管,并在大气压下加水。为了阐明外管长度对环空传热结果的影响,将其与单个无限制管的数据进行了比较。外管长度的变化导致传热系数的很大变化。当外管长度为0.2 m时,由于气泡聚结强度的降低,传热系数的劣化点上升到更高的热通量。