首页> 外文期刊>Letters in heat and mass transfer >Use of RF electric fields for simultaneous mineral and bio-fouling control in a heat exchanger
【24h】

Use of RF electric fields for simultaneous mineral and bio-fouling control in a heat exchanger

机译:使用RF电场同时控制热交换器中的矿物和生物污染

获取原文
获取原文并翻译 | 示例
           

摘要

The objective of the present study was to investigate the effectiveness of a physical water treatment (PWT) technology using oscillating RF (radio frequency) electric fields in water to mitigate both mineral and bio-fouling in a cooling water application. Heat transfer tests were conducted using a laboratory-scale cooling tower to determine fouling resistance over time, and bio-fouling tests were performed using a heterotrophic plate count method to measure colony forming units (CFU) values per milliliter of cooling water. The results indicated that the present PWT technology could provide an effective mineral fouling prevention by maintaining 90% of the peak heat transfer performance of a heat exchanger, while effectively controlling water-borne microbial organisms.
机译:本研究的目的是研究物理水处理(PWT)技术的有效性,该技术使用水中的振荡RF(射频)电场来减轻冷却水应用中的矿物污染和生物污染。使用实验室规模的冷却塔进行传热测试,以确定随时间的结垢阻力,并使用异养平板计数法进行生物结垢测试,以测量每毫升冷却水的菌落形成单位(CFU)值。结果表明,当前的PWT技术可以通过保持热交换器的峰值传热性能的90%来提供有效的矿物结垢预防,同时有效地控制水性微生物。