This article introduces a novel method for integrating arc-flash analysis with protective device coordination on time-current coordination (TC) plots. A new concept, called the human damage curve (HDC), is included in the coordination process, which relates directly to calories/cm2 energy levels of personal protective equipment (PPE). Each curve in an HDC family holds to a set of consistent arc-flash assumptions based on those found in the National Electrical Safety Code (NESC) and IE 1584 standards. That set of assumptions includes values for the working distance, voltage level, arc gap width, open air/cabinet conditions, and the full consideration of escape time.
机译:本文介绍了一种新的方法,该方法可将弧闪分析与时间-电流协调(TC)图上的保护设备协调相集成。协调过程中包含了一个称为人为伤害曲线(HDC)的新概念,该概念直接与个人防护设备(PPE)的卡路里/ cm2能量水平相关。 HDC系列中的每条曲线均根据美国国家电气安全规范(NESC)和IE 1584标准中的假设,遵循一组一致的弧闪假设。该组假设包括工作距离,电压水平,电弧间隙宽度,露天/柜内条件以及对逃逸时间的充分考虑的值。