A Case Study of Voltage Transformer Failures: Solution Implementation in a Modern Data Center

机译:电压互感器故障的案例研究:现代数据中心的解决方案实施

获取原文
获取原文并翻译 | 示例
           

摘要

While preparing a modern data center for startup, the commissioning process involved primary circuit switching that resulted in two voltage transformer (VT) failures. As a result, we conducted a comprehensive investigation of the VT failures. As the investigation proceeded, VT ferroresonance on circuit opening and high-frequency switching transients on closing emerged as possible root causes of the failures. After incorporating extensive transient simulations and three rounds of field transient measurements, we designed and implemented a complete solution that included the sizing of snubbers to overcome excessive switching transients and the development of a saturable reactor to protect VTs against the effects of ferroresonance. This article describes the root causes, simulations, field measurements, recommended solutions, and solution implementation for this event. The correlation between field measurements and simulation results shows the effectiveness of modeling the implemented solutions.
机译:在准备启动现代化数据中心时,调试过程涉及一次电路切换,这导致两个电压互感器(VT)出现故障。因此,我们对VT故障进行了全面调查。随着调查的进行,可能出现故障的根本原因是电路断开时的VT铁磁谐振和闭合时的高频开关瞬变。在结合了广泛的瞬态仿真和三轮现场瞬态测量之后,我们设计并实施了一个完整的解决方案,其中包括确定缓冲器大小以克服过多的开关瞬态,以及开发可饱和电抗器以保护VT免受铁磁谐振的影响。本文介绍了此事件的根本原因,模拟,现场测量,推荐的解决方案和解决方案实施。现场测量结果与仿真结果之间的相关性表明了对已实施解决方案建模的有效性。