Grounding the Neutral of Electrical Systems Through Low-Resistance Grounding Resistors: An Application Case

机译:通过低电阻接地电阻将电气系统的中性点接地:一个应用案例

获取原文
获取原文并翻译 | 示例
           

摘要

It seems common knowledge that three-phase short-circuit currents are the worst possible scenario for electrical systems. In reality, single-phase ground-fault currents may be significantly more intense than three-phase fault currents. With the occurrence of high single-phase fault currents, severe damage could be caused to the iron cores of electric machines included in the zero-sequence fault loop. The method of neutral low-resistance grounding will be discussed by applying a step-by-step calculation procedure to an actual case, in order to properly size the grounding resistor, thereby limiting the fault current.
机译:众所周知,三相短路电流是电气系统中最糟糕的情况。实际上,单相接地故障电流可能比三相故障电流的强度大得多。随着高单相故障电流的出现,可能会对零序故障回路中包含的电机的铁芯造成严重损坏。中性低电阻接地的方法将通过对实际情况应用逐步的计算过程进行讨论,以便适当选择接地电阻的大小,从而限制故障电流。