首页> 外文期刊>Industry Applications, IEEE Transactions on >DC Bus Voltage Clamp Method to Prevent Over-Voltage Failures in Adjustable Speed Drives
【24h】

DC Bus Voltage Clamp Method to Prevent Over-Voltage Failures in Adjustable Speed Drives

机译:直流母线电压钳位方法可防止变速驱动器发生过压故障

获取原文
获取原文并翻译 | 示例
           

摘要

The influences of PWM switching and long cable length on motor insulations have been discussed in numerous papers. This paper investigates their effect on the voltage insulation components inside an adjustable speed drive (ASD). This paper shows that high potential voltage insulation issue may exist on various components inside the ASD and cause earlier failures under very long cable or multiple drive conditions. A system model to describe this phenomenon is described in the paper. A dc bus voltage clamp circuit is proposed to reduce these voltage stresses. The effectiveness of this circuit is verified by both simulation and experimental results.
机译:在许多论文中已经讨论了PWM切换和长电缆长度对电机绝缘的影响。本文研究了它们对变速驱动器(ASD)内部的电压绝缘组件的影响。本文表明,在非常长的电缆或多种驱动条件下,ASD内部的各个组件上可能存在高电压绝缘问题,并且会导致较早的故障。本文描述了描述这种现象的系统模型。提出了一种直流总线电压钳位电路来减小这些电压应力。仿真和实验结果均验证了该电路的有效性。