Tripping Characteristics of Residual Current Devices Under Nonsinusoidal Currents

机译:非正弦电流下剩余电流装置的跳闸特性

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents an experimental investigation into the operating characteristics of residual current devices (RCDs) under an unbalanced current. The unbalanced current included the harmonic current, ground fault current, and surge current. A testing system was first set up in the laboratory, and the minimum values of the current causing RCD samples to trip were recorded. To obtain consistent testing results, RCD samples under test were demagnetized prior to each test. It is found that RCD tripping is primarily determined by the peak value of the unbalanced current. Under a ground fault, RCDs installed in healthy circuits may trip. It would be necessary to limit the maximum leakage current in the circuits to avoid such nuisance tripping. Under surge conditions, RCDs could withstand a large short-duration current. However, a long-duration surge current can easily cause RCDs to trip.
机译:本文提出了对不平衡电流下剩余电流设备(RCD)的工作特性的实验研究。不平衡电流包括谐波电流,接地故障电流和浪涌电流。首先在实验室中建立了一个测试系统,并记录了引起RCD样品跳闸的最小电流。为了获得一致的测试结果,被测RCD样品在每次测试前都要消磁。发现RCD跳闸主要由不平衡电流的峰值确定。在接地故障下,安装在正常电路中的RCD可能会跳闸。有必要限制电路中的最大泄漏电流,以避免这种麻烦的跳闸。在浪涌条件下,RCD可以承受较大的短时电流。但是,长时间的浪涌电流很容易导致RCD跳闸。