In large power transformers, the presence of stray currents in the structural elements near the high current bushings can be considerable, and this leads to hot spots. This work presents a practical analysis of overheating in the bolts that join the tank and the cover, which are near the high current bushings of the transformer. Overheating results are analyzed and discussed for the case of a 420-MVA transformer. The hot spots in the flange-bolt regions are discovered by thermal maps that are obtained during power transformer operation as a part of a preventive maintenance program. In this paper, we use copper links to ensure the connection of both the cover and tank body, significantly reducing the overheating of the flange-bolt region. The copper link solution has been validated by measurements. We have used calibrated measurement instruments in all the experiments. Moreover, a 3-D finite-element analysis of the geometry of interest has been used to verify the copper link solution.
机译:在大型电力变压器中,大电流套管附近的结构元件中会存在大量杂散电流,这会导致热点。这项工作提出了对连接罐和盖的螺栓中的过热的实际分析,这些螺栓靠近变压器的大电流套管。对于420 MVA变压器的情况,对过热结果进行了分析和讨论。法兰螺栓区域中的热点是通过热图发现的,该图是在电力变压器运行期间作为预防性维护程序的一部分而获得的。在本文中,我们使用铜链来确保盖和罐体的连接,从而大大减少了法兰螺栓区域的过热。铜链路解决方案已通过测量验证。我们在所有实验中都使用了校准过的测量仪器。此外,对所关注几何形状的3D有限元分析已用于验证铜链解决方案。