During the transient period at the start of a voltage sag, a DVR injection transformer can experience a flux-linkage that is up to twice its nominal steady-state value. In order to prevent the transformers from saturating it is normal to choose a rating flux that is double that of the steady-state limit. An alternative method is to limit the flux-linkage during the transient switch-on period, thus preventing saturation. It is shown through both simulation and experimental results that an adaptive form factor can be applied to the DVR injected voltage, which minimizes the disturbance seen by a sensitive load, while at the same time preventing saturation. The proposed method removes the need for rating the series injection transformers for the DVR transient switch-on period, and therefore removes the redundancy normally associated with their steady state operation. In economic terms, this may reduce the total cost of a DVR system, thus making it a more attractive solution for voltage sag mitigation.
机译:在电压骤降开始的瞬态期间,DVR注入变压器可能会遇到高达其标称稳态值两倍的磁链。为了防止变压器饱和,通常选择的额定通量是稳态极限值的两倍。另一种方法是在瞬态接通期间限制磁链,从而防止饱和。通过仿真和实验结果表明,可以将自适应形状因数应用于DVR注入电压,从而最大程度地减小敏感负载所受的干扰,同时防止饱和。所提出的方法消除了在DVR瞬态接通期间为串联注入变压器定额的需要,因此消除了通常与它们的稳态工作相关的冗余。从经济角度来讲,这可以降低DVR系统的总成本,从而使其成为减轻电压骤降的更具吸引力的解决方案。