Commercial installations of voltage-source converter-high voltage direct current (VSC-HVDC) are now in service as asynchronous link and as underwater/underground dc transmission. The research reported in this paper is directed to providing VSC-HVDC with synchronizing power and damping power so that after a transient, the steady-state is reached in minimal time. Damping power is achieved by injecting incremental power which is proportional to the frequency deviation measured by a phase lock loop. Synchronizing power is achieved by: 1) introducing a delay in the power measurement and 2) by incorporating a static synchronous series compensation in the VSC-station. The effectiveness of both the synchronizing and damping power is demonstrated through digital simulations of a turbine-generator system which is connected to a VSC-HVDC Station. It is shown that with the synchronizing power and damping power, recovery from the fault disturbance is very much faster.
机译:电压源转换器-高压直流电(VSC-HVDC)的商业安装现已用作异步链路和水下/地下dc传输。本文报道的研究旨在为VSC-HVDC提供同步功率和阻尼功率,以便在瞬变之后,在最短的时间内达到稳态。通过注入与锁相环测得的频率偏差成比例的增量功率来实现阻尼功率。通过以下方法实现同步功率:1)在功率测量中引入延迟,以及2)在VSC站中加入静态同步串联补偿。通过与VSC-HVDC站相连的涡轮发电机系统的数字仿真,证明了同步功率和阻尼功率的有效性。结果表明,利用同步功率和阻尼功率,从故障扰动中恢复要快得多。