首页> 外文期刊>IEEE Computer Applications in Power >Computing overhead line parameters
【24h】

Computing overhead line parameters

机译:计算架空线参数

获取原文
获取原文并翻译 | 示例
           

摘要

This study focuses on the computation of line constants at the power line frequencies of 50 and 60 Hz. At this frequency range, computer methods and handbook formulas give virtually identical positive-sequence impedances, with the exception of overhead lines with ground wires. A study by H. Dommel (1985) confirmed that the positive-sequence impedance given by the two methods are usually within a small fraction of 1%, a difference that is negligible compared to the uncertainties in the physical parameters. But in cases where ground wires are present, the study showed a substantial difference between the results of handbook formulas and those of computer programs. The recent availability of graphical user interfaces has prompted the development of line-constraints programs that use interactive graphics. One such program, called the ASPEN Line Constants Program, is described briefly. This description illustrates the typical inputs to a line constants program.
机译:这项研究的重点是在50和60 Hz的电源线频率下的线常数的计算。在此频率范围内,计算机方法和手册公式会给出几乎相同的正序阻抗,但带有接地线的架空线除外。 H. Dommel(1985)的一项研究证实,两种方法给出的正序阻抗通常在1%的很小范围内,与物理参数的不确定性相比,这一差异可以忽略不计。但是,在存在接地线的情况下,研究表明手册公式的结果与计算机程序的结果之间存在很大差异。图形用户界面的最新可用性促使开发了使用交互式图形的线约束程序。简要描述了一个这样的程序,称为ASPEN线常数程序。该描述说明了线常数程序的典型输入。