The electrical distribution boards and control cubicles, installed inside the ITER tokamak building, can be subjected to a constant or slowly variable magnetic field up to 70mT, l0mT/s induced by ITER coils. This is a very unusual environmental condition and there are almost no data available on static magnetic field compatibility for the standard industrial, electrical and electronic components, usually installed inside standard low voltage distribution boards and standard control boards. A series of tests has therefore been envisaged, in collaboration with EFDA close support unit [I. Benfatto, P. Bettini, M. Cavinato, A. De Lorenzi, J. Hourtoule, E. Serra, Magnetic compatibility of standard components for electrical installations: computation of the background field and consequences on the design of the electrical distribution boards and control boards for the ITER tokamak building, SOFT Conference Presentation, Venice, September 2004] and the Consorzio RFX [L. Grando, A. De Lorenzi, G. Bettanini, D. Desideri, Magnetic compatibility of standard components for electrical installations: tests on low voltage circuit breakers and contactors, SOFT Conference Presentation, Venice, September 2004], to assess the operational limits of these components. CEA has especially taken in charge the test of electronic, control and signal conditioning units. On this subject, a test bed composed of a solenoid and a 30 V, 800 A power supply, has been developed at CEA Cadarache. Its characteristics are the following: Magnetic field capability: 140 mT Variation of field: up to l0mT/s Useful dimensions for equipment under test: 500 mm x 500 mm x 500 mm The list of the components to be tested has been identified trying to find common and recent components of different manufacturers. Test procedures have been written following the most relevant IEC standards and manufacturing recommendations and procedures.Magnetic compatibility tests on the basic components of standard low voltage control boards have been performed. All components tested are more or less sensitive to magnetic fields and the effect varies from the simple perturbation of the output signals to the partial destruction of some electronic card. The most sensitive are the ferromagnetic components like small power supply transformers, relays, inductors, etc. For power supplies, the most important consequence is the increase of the consumption (primary current). For most of the conditioning units (signal treatment), the operational limits were found in the range of 30 mT (destruction of power supply filter by over current and overload of the supply). For PLC central units tested, the limit is in the order of 40 mT (components permanently out of service). Relays are limited to 15 mT (outputs oscillations, no commutation). The paper will present, in detail, the methods and the results of these tests giving recommendations for future analysis.
机译:安装在ITER托卡马克大楼内的配电板和控制柜可受到ITER线圈感应的恒定磁场或缓慢变化的磁场,最高70mT,10mT / s。这是一个非常不寻常的环境条件,几乎没有关于标准工业,电气和电子组件的静磁场兼容性的数据,这些组件通常安装在标准低压配电板和标准控制板内部。因此,与EFDA密切支持部门合作,已经设想了一系列测试。 Benfatto,P.Bettini,M.Cavinato,A.De Lorenzi,J.hourtoule,E.Serra,《电气安装标准组件的磁兼容性:背景场的计算以及对配电板和控制板设计的影响用于ITER托卡马克大楼,SOFT会议演示,威尼斯,2004年9月]和Consorzio RFX [L. Grando,A。De Lorenzi,G。Bettanini,D。Desideri,电气设备标准组件的磁兼容性:低压断路器和接触器的测试,SOFT Conference Presentation,威尼斯,2004年9月,以评估这些设备的操作极限组件。 CEA特别负责电子,控制和信号调节单元的测试。在这个问题上,CEA Cadarache开发了一个由螺线管和30 V,800 A电源组成的测试台。它的特性如下:磁场能力:140 mT磁场变化:高达10 mT / s被测设备的有用尺寸:500 mm x 500 mm x 500 mm试图找出要测试的组件清单不同制造商的通用组件和最新组件。遵循最相关的IEC标准以及制造建议和程序编写了测试程序,并已对标准低压控制板的基本组件进行了电磁兼容性测试。所有测试的组件或多或少都对磁场敏感,其影响范围从输出信号的简单扰动到某些电子卡的部分破坏。最敏感的是铁磁组件,例如小型电源变压器,继电器,电感器等。对于电源,最重要的后果是功耗(一次电流)的增加。对于大多数调节单元(信号处理),发现其运行极限为30 mT(过电流和电源过载对电源滤波器的破坏)。对于已测试的PLC中央单元,该限制约为40 mT(组件永久停用)。继电器限制为15 mT(输出振荡,无换向)。本文将详细介绍这些测试的方法和结果,为将来的分析提供建议。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号