North American smoke-alarm installation standards and manufacturer's recommendations require that smoke alarms be installed not less than 100 mm from any adjoining wall if mounted on a flat ceiling, and not closer than 100 mm and not farther than 300 mm from the adjoining ceiling surface if mounted on walls. The aim of this prescriptive rule is to avoid installation of smoke alarms in the "dead air space", where it is assumed to be difficult for smoke to reach. However, there was little scientific basis and experimental evidence for this prescriptive rule. A series of experimental studies were conducted in a residential dwelling as well as in a laboratory room to examine the effect of "dead air space" on smoke-alarm response. Small and slow-growing smouldering and flaming fire sources were used to challenge the smoke alarms. The results show that smoke can reach the "dead air space" under the experimental conditions and the smoke alarms installed in the "dead air space" can respond to the fire at times comparable to, and in many cases even earlier than, the smoke alarms installed at conventional locations. There was no obvious evidence of the "dead air space" effect. The prescriptive "dead air space" as currently defined in the standards is questionable as far as early fire detection is concerned when fires are still small and smoke flows caused by the fires are still slow. Performance-based approaches should be used to identify those spaces where smoke may be difficult to reach.
机译:北美烟雾警报安装标准和制造商的建议要求,如果将烟雾警报器安装在平坦的天花板上,则烟雾警报器的安装距离相隔壁应不少于100 mm;如果烟雾警报器安装在平坦的天花板上,则应距离相隔天花板不小于100 mm且不大于300 mm安装在墙上。此规范性规则的目的是避免在“死空气空间”中安装烟雾报警器,而在“死空气空间”中,烟雾很难到达。但是,该规定规则缺乏科学依据和实验证据。在住宅和实验室中进行了一系列实验研究,以研究“死气空间”对烟雾警报响应的影响。小型且生长缓慢的阴燃和火焰源被用来挑战烟雾报警器。结果表明,在实验条件下,烟雾可以到达“死气空间”,并且安装在“死气空间”中的烟雾报警器有时可以甚至甚至早于烟雾报警器对火灾做出响应。安装在常规位置。没有明显的证据表明“死气空间”的影响。当火灾仍然很小并且火灾引起的烟流仍然很慢时,标准中当前定义的规定性“死气空间”对于早期火灾探测是有问题的。应采用基于性能的方法来识别可能难以到达烟雾的空间。

著录项

  • 来源
    《Fire Technology》 |2009年第1期|97-115|共19页
  • 作者单位

    Fire Research Program, Institute for Research in Construction, National Research Council of Canada, Bldg. M59, 1200 Montreal Road, Ottawa, ON, Canada K1A 0R6;

    Fire Research Program, Institute for Research in Construction, National Research Council of Canada, Bldg. M59, 1200 Montreal Road, Ottawa, ON, Canada K1A 0R6;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    smoke alarms; fire detection;

    机译:烟雾报警器;火灾探测;