Bare-bead thermocouples are widely used for measuring temperature fields in compartment fires. It is well-known that temperature readings using such a device can be significantly affected by radiation errors, the apparent thermocouple junction temperature being thus different from the true gas temperature. However, a probe consisting of two thermocouples of unequal diameters, but made of the same material can be used for estimating the gas temperature in a fire environment. Using a steady-state heat transfer model applicable to a bare-bead thermocouple, a very simple rule is proposed for the estimation of radiation errors when temperatures are measured by use of two thermocouples of different diameters. Radiation errors obtained from this simple rule are compared and discussed with experimental results involving a compartment fire with pyridine as the fuel.
机译:裸珠热电偶广泛用于测量舱室火灾中的温度场。众所周知,使用这种设备的温度读数会受到辐射误差的显着影响,因此表观热电偶结温与真实气体温度不同。但是,由两个不等直径但由相同材料制成的热电偶组成的探头可用于估算火灾环境中的气体温度。使用适用于裸珠热电偶的稳态传热模型,提出了一个非常简单的规则来估算当使用两个不同直径的热电偶测量温度时的辐射误差。比较和讨论了从该简单规则获得的辐射误差,并与涉及以吡啶为燃料的舱室火灾的实验结果进行了讨论。