Reinforced concrete and fiber reinforced concrete panels subjected to blast detonations and post-blast static tests

机译:经受爆炸和爆炸后静力测试的钢筋混凝土和纤维钢筋混凝土板

获取原文
获取原文并翻译 | 示例
           

摘要

Results of an experimental study of reinforced concrete panels under blast detonations are presented. The primary purpose of the tests was to collect data for validating simulation methods for blast loads. The scaled distance ranged from 0.41 m/(kg)~(1/3) to 0.57 m/(kg)~(1/3) and hence the tests are close-in detonations. Four types of 1.2 m square panels were subjected to blast to investigate the performance of new walls: reinforced concrete (RC) panels; fiber reinforced concrete (FRC) panels without additional reinforcement; FRC panels reinforced with steel bars; and RC panels reinforced with glass fiber reinforced polymer (GFRP) bars. Another RC panel type was built which was retrofitted with external GFRP laminates on both faces. The performance of the panels is classified into three categories as medium protection, very low protection, and protection below antiterrorism standards. FRC panels reinforced with steel bars had the best performance for new construction. Panels that survived the blast detonation without sustaining a breach were tested under monotonic static loads to determine their static post-blast load resistance.
机译:给出了爆炸下钢筋混凝土板的实验研究结果。测试的主要目的是收集数据,以验证爆炸载荷的模拟方法。标度距离范围从0.41 m /(kg)〜(1/3)到0.57 m /(kg)〜(1/3),因此测试是近距离爆轰。对四种类型的1.2 m方形面板进行了爆炸处理,以研究新墙的性能:钢筋混凝土(RC)面板;纤维增强混凝土(FRC)面板,无需额外增强;用钢筋加固的FRC面板;玻璃纤维增​​强聚合物(GFRP)钢筋加固的RC面板。建造了另一种RC面板类型,在两面都加装了外部GFRP层压板。小组的表现可分为三类:中等保护,极低保护和低于反恐怖主义标准的保护。用钢筋加固的FRC面板在新建建筑中具有最佳性能。在单调静态载荷下测试了在爆炸爆炸中幸存下来的面板,并在单调静态载荷下进行了测试,以确定其静态的爆炸后载荷阻力。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号