首页> 外文期刊>IEEE Transactions on Electrical Insulation >Natural insulator contamination test results on various shed shapes in heavy industrial contamination areas
【24h】

Natural insulator contamination test results on various shed shapes in heavy industrial contamination areas

机译:在重工业污染区中各种绝缘子形状的天然绝缘子污染测试结果

获取原文
获取原文并翻译 | 示例
           

摘要

In Shanghai, China, industrial contamination is very severe and periodic insulator washing is performed not only in substations but also on transmission lines. In order to review the present insulator contamination design and maintenance practices, a series of periodical contamination measurements under de-energized conditions were made. Also insulators that had been energized at two sites for one year were removed, and withstand voltage tests were conducted in an artificial fog chamber. Unexpectedly high ESDD (Equivalent Salt Deposit Density) values <1 mg/cm/sup 2/ and NSDD (Nonsoluble Deposit Density) values over <5 mg/cm/sup 2/ were measured. Aerodynamic type insulators showed a smaller accumulation of contamination than deep-rib type insulators. However, no significant difference can be seen between aerodynamic type and deep-rib type insulators in the withstand voltage per unit insulator string length. CaSO/sub 4/1/2H/sub 2/O (Bassanite) is identified as the most dominant soluble contaminant.
机译:在中国上海,工业污染非常严重,不仅在变电站而且在输电线路上都要定期进行绝缘子清洗。为了回顾当前的绝缘子污染设计和维护实践,在断电条件下进行了一系列定期的污染测量。还将在两个位置上通电了一年的绝缘子移开,并在人造雾室中进行了耐压测试。测得的异常高的ESDD(等效盐沉积密度)值<1 mg / cm / sup 2 /和NSDD(非可溶性沉积物密度)值超过5 mg / cm / sup 2 /。空气动力型绝缘子比深肋型绝缘子显示出较小的污染物积累。但是,在空气动力型绝缘子和深肋型绝缘子之间,在每单位绝缘子串长度的耐压方面没有发现显着差异。 CaSO / sub 4/1 / 2H / sub 2 / O(Bassanite)被确定为最主要的可溶性污染物。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号