首页> 外文期刊>IEE proceedings. Part C >Capacitor placement in radial distribution systems for loss reduction
【24h】

Capacitor placement in radial distribution systems for loss reduction

机译:电容器放置在径向配电系统中以减少损耗

获取原文
获取原文并翻译 | 示例
           

摘要

Reduction of I/sup 2/R loss in distribution systems is very essential to improve the overall efficiency of power delivery. The I/sup 2/R loss can be separated into two parts based on the active and reactive components of branch currents. The paper presents a method of minimising the loss associated with the reactive component of branch currents by placing shunt capacitors. This method first determines a sequence of nodes to be compensated by capacitors. The size of the optimal capacitor at the compensated nodes is then determined by optimising the loss saving equation with respect to the capacitor currents. The performance of the proposed method was investigated on two distribution systems consisting of 15 and 33 buses and it was found that a significant loss saving can be achieved by placing optimal capacitors in the system.
机译:降低配电系统中的I / sup 2 / R损耗对于提高电源的整体效率非常重要。根据分支电流的有功和无功分量,I / sup 2 / R损耗可分为两部分。本文提出了一种通过放置并联电容器来最小化与支路电流的无功分量相关的损耗的方法。该方法首先确定要由电容器补偿的节点序列。然后,通过针对电容器电流优化损耗节省方程式,确定补偿节点处最佳电容器的尺寸。在由15和33条母线组成的两个配电系统上研究了该方法的性能,发现通过在系统中放置最佳电容器可以大大节省损耗。