【24h】

Investigation on the regulating methods of air source heat pump system used for district heating: Considering the energy loss caused by frosting and on-off

机译:用于区供暖的空气源热泵系统调节方法的研究:考虑到磨砂和开关引起的能量损失

获取原文
获取原文并翻译 | 示例
           

摘要

Air source heat pump (ASHP) has been used in Northern China for district heating. However, few investigations on its regulating methods have been conducted till now. To increase the energy-saving effect of AHSPs, a simulation model, which considered the energy loss caused by frosting and on-off, was developed in this paper. Based on this model, three combination regulating modes suitable for district heating using ASHPs as heating source were proposed. Then the heating performance of ASHPs used for district heating in seven cities was investigated using this model. Results showed that both the energy loss corrections of frosting and on-off have evident impacts on the power consumption and seasonal coefficient of performance (SCOP). Owing to the energy loss correction of frosting, the power consumption of ASHP unit is increased by 3.85%-17.41%, and meanwhile SCOP is decreased by 3.72%-14.83%. The influence of the energy loss of on-off decreases gradually with the increase of heating area. In the three regulating modes, the power consumption of ASHP unit changes slightly, while the energy saving rate of water pump can reach 80.97%-86.46%. When the pitch of buried pipe was 300 mm, ASHP can meet the heating demand in all the three regulating modes. (c) 2021 Elsevier B.V. All rights reserved.
机译:空气源热泵(ASHP)已在中国北部进行地区供暖。但是,迄今为止已经对其调节方法进行了很少的调查。为了提高AHSP的节能效果,本文开发了一种考虑通过磨损和开关引起的能量损失的仿真模型。基于该模型,提出了适用于使用ASHPS作为加热源的区域加热的三种组合调节模式。然后,使用该模型研究了七个城市的分区供暖的ASHP的加热性能。结果表明,结霜和开关的能量损失校正都显着影响了对功耗和季节性的性能系数(SCOP)。由于磨砂的能量损失校正,ASHP单元的功耗增加了3.85%-17.41%,同时SCOP降低了3.72%-14.83%。随着加热区域的增加,开关能量损失的影响逐渐降低。在三种调节模式中,ASHP单元的功耗略有变化,而水泵的节能速率可达80.97%-86.46%。当埋管的间距为300毫米时,ASHP可以在所有三种调节模式下满足加热需求。 (c)2021 Elsevier B.v.保留所有权利。

著录项

  • 来源
    《Energy and Buildings》 |2021年第3期|110731.1-110731.10|共10页
  • 作者单位

    Harbin Inst Technol Minist Ind & Informat Technol Key Lab Cold Reg Urban & Rural Human Settlement E Sch Architecture Harbin Peoples R China;

    Harbin Inst Technol Minist Ind & Informat Technol Key Lab Cold Reg Urban & Rural Human Settlement E Sch Architecture Harbin Peoples R China;

    Harbin Inst Technol Minist Ind & Informat Technol Key Lab Cold Reg Urban & Rural Human Settlement E Sch Architecture Harbin Peoples R China;

    Harbin Inst Technol Minist Ind & Informat Technol Key Lab Cold Reg Urban & Rural Human Settlement E Sch Architecture Harbin Peoples R China;

    Harbin Inst Technol Minist Ind & Informat Technol Key Lab Cold Reg Urban & Rural Human Settlement E Sch Architecture Harbin Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Air source heat pump; District heating; Regulating modes; Energy loss of frosting; Energy loss of on-off;

    机译:空气源热泵;区供暖;调节模式;糖霜的能量损失;开关的能量损失;
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号