The medium-depth geothermal heat pump systems (MD-GHPs) use vertical concentric deep borehole heat exchangers (DBHEs) with depth more than 2 km to extract heat from medium-depth geothermal energy, which provides a higher-temperature heat source and improve the energy performance of heat pump obviously. This paper introduces the field test on energy performance of heat pumps in MD-GHPs. Results show that the outlet and inlet water temperature of DBHEs reach 33.0 degrees C and 23.7 degrees C respectively, thus the COP of heat pumps reaches 5.70. However, the heat pump with constant speed compressor is identified unsuitable for operation with high-temperature heat source. Besides, the high water resistance, low water temperature difference and energy efficiency lead to the poor energy performance of water pumps. Thus the high-temperature heat source hasn't been fully utilized. Then based on analysis of field test results, the design parameters of heat pump are optimized and the variable speed centrifugal compressor is applied. While the design parameters and control strategy of water pumps are optimized. Finally, the optimization effect is examined through practical application and the SPFH1, WTFu, WTFg, SPFH3, and SPFH4 of MD-GHPs reach 7.71, 57.2, 97.6, 7.15 and 6.35 separately, which are obviously improved. (C) 2019 Elsevier B.V. All rights reserved.
机译:中深地热泵系统(MD-GHPS)使用垂直同心深层钻孔热交换器(DBHOS),深度超过2公里,以从中深的地热能提取热量,这提供了更高温度的热源并改善了热泵的能量性能明显。本文介绍了MD-GHP中热泵能量性能的现场测试。结果表明,DBHES的出口和入口水分分别达到33.0摄氏度和23.7摄氏度,因此热泵COP达到5.70。然而,具有恒定速度压缩机的热泵被识别不适合高温热源的操作。此外,高耐水性,低水温差和能效导致水泵的能量性能差。因此,高温热源尚未充分利用。然后基于对现场测试结果的分析,优化了热泵的设计参数,施加了变速离心压缩机。虽然水泵的设计参数和控制策略进行了优化。最后,通过实际应用和SPFH1,WTFU,WTFG,SPFH3和MD-GHPS达到7.71,57.2,97.6,7.15和6.35的SPFH1,WTFU,WTFG,SPFH3和SPFH4进行了检查,这显然是改进的。 (c)2019 Elsevier B.v.保留所有权利。

著录项

  • 来源
    《Energy and Buildings》 |2020年第2期|109724.1-109724.14|共14页
  • 作者单位

    Univ Beijing Dept Bldg Sci Beijing 100084 Peoples R China;

    Univ Beijing Dept Bldg Sci Beijing 100084 Peoples R China;

    Univ Beijing Dept Bldg Sci Beijing 100084 Peoples R China;

    Shaanxi Sijichun Clean Energy Co Ltd Xian 710000 Peoples R China;

    GREE Elect Appliances INC SKL Air Conditioning Equipment & Syst Energy Cons Zhuhai 519070 Peoples R China;

    GREE Elect Appliances INC SKL Air Conditioning Equipment & Syst Energy Cons Zhuhai 519070 Peoples R China;

    Univ Beijing Dept Bldg Sci Beijing 100084 Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Medium-depth geothermal energy; Heat pumps; Field tests; Design parameters; System optimization;

    机译:中深的地热能;热泵;现场测试;设计参数;系统优化;

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号