Results and conclusions are presented from 22 staged fault tests made on a 154-kv transmission line and terminal systems to check the characteristics of new long-line relays, discussed in companion papers,1,2 which were designed to differentiate between faults and high power swings. Observed power swings and relay performance are compared with theoretical aspects and predictions. Data on the transientstability limit of the interconnection, together with observations made during the tests, are also presented. Measured values of line constants and short and open-circuit impedances are given, together with results of attenuation tests at carrier frequencies. Manner of initiating the faults, scheduling of power flows, and organizing personnel are briefly discussed.
机译:通过在154 kV输电线路和终端系统上进行的22阶段故障测试,得出了结果和结论,以检查新型长线继电器的特性,该论文在随附的论文 1,2 中进行了讨论。区分故障和大功率摆幅。将观察到的功率摆幅和继电器性能与理论方面和预测进行了比较。还提供了有关互连的瞬态稳定性极限的数据,以及在测试过程中所做的观察。给出了线路常数,短路和开路阻抗的测量值,以及载频上的衰减测试结果。简要讨论了启动故障,调度潮流和组织人员的方式。