Loading of closed delta banks of substation transformers to a point approaching safe thermal limit results in severe overloading of two transformers as well as decided unbalance in voltage and current when operated in open delta as a result of the failure of one transformer. By the use of mobile capacitor units with capacitors arranged in two unequal groups, the load on two transformers in open delta is reduced, regulation improved, voltage and current are balanced within operating limits, and with the aid of fans, the top oil temperatures — and consequently, the copper temperatures — are kept within safe limits. This permits proper loading of transformers in closed delta, a relatively short interruption to service or reduction in load upon failure of one transformer in a bank, and a reduction in number of transformers required for emergency use.
机译:变电站变压器的闭合三角洲负载加载到接近安全热极限的点会导致两台变压器严重过载,并且由于一台变压器的故障而导致在开放三角洲运行时电压和电流的确定不平衡。通过使用带有两个不相等组的电容器的移动电容器单元,可以减少开式三角形中两个变压器的负载,改善调节,在工作范围内平衡电压和电流,并借助风扇,达到最高油温-因此,铜的温度保持在安全范围内。这可以使变压器以闭合的三角形进行适当的负载,在组中的一台变压器发生故障时可以相对较短地中断服务或减少负荷,并可以减少紧急使用所需的变压器数量。