Substation grounding systems typically build up a large network of various grounding electrodes, which consists of a substation grounding grid, multi-grounded transmission line skywires and distribution line neutral wires. Although the fall-of-potential (FOP) method has been widely used for ground resistance measurement, it is difficult to use the method in case of such a substation grounding system because of the difficulty of interpretation of the measured FOP profile. In this paper, we have presented a practical example of ground resistance measurement in a 154kV substation under commercial operating condition. Conventional FOP tests and the measurement of ground current splits to each part of the grounding system were conducted simultaneously. A simple interpretation method of FOP profiles, with the measured ground current splits, has been suggested.
机译:变电站接地系统通常会建立一个由各种接地电极组成的大型网络,该网络由变电站接地网,多接地传输线天线和配电线中性线组成。尽管电位降(FOP)方法已广泛用于接地电阻测量,但是在变电站接地系统的情况下,由于难以解释测得的FOP轮廓而很难使用该方法。在本文中,我们提供了一个在商业运行条件下154kV变电站接地电阻测量的实际示例。同时进行常规的FOP测试和对接地系统各部分的接地电流分配的测量。已经提出了一种简单的解释FOP曲线的方法,包括测量的接地电流。