首页> 外文期刊>Electric power systems research >Lightning protection of overhead transmission lines using external ground wires
【24h】

Lightning protection of overhead transmission lines using external ground wires

机译:使用外部接地线的架空输电线路的防雷保护

获取原文
获取原文并翻译 | 示例
           

摘要

In this paper, a new kind of overhead transmission line (OHL) lightning protection system based on external ground wires is analyzed. Instead of a standard ground wire, two ground wires placed at the top of separate external towers located at both sides of the protected line are used. This type of protection should be applied in specific circumstances for protection of short OHL sections which are highly endangered by lightning. The distance between external protection system and OHL is calculated by using EMTP-ATP. Calculations are performed in order to avoid flashovers from the point where lightning strikes the external protection system to the protected OHL. A rolling sphere method is used to calculate the height of external ground wires above OHL phase conductors to avoid shielding failures. An experiment in a high voltage laboratory is performed to verify the dimensions of the external protection system from the aspect of shielding failures. According to the results of simulation and experiment, the optimal dimensions of the external protection system are determined. (C) 2015 Elsevier B.V. All rights reserved.
机译:本文分析了一种基于外部接地线的新型架空输电线路防雷系统。代替标准接地线,使用两条接地线放置在位于受保护线路两侧的独立外部塔架的顶部。此类保护措施应在特殊情况下用于保护受到闪电高度威胁的短OHL区域。外部保护系统与OHL之间的距离是使用EMTP-ATP计算的。进行计算是为了避免从雷击外部保护系统到受保护的OHL的闪络。滚动球法用于计算OHL相导体上方外部接地线的高度,以避免屏蔽故障。在高压实验室中进行了一项实验,从屏蔽故障的角度验证了外部保护系统的尺寸。根据仿真和实验结果,确定了外部保护系统的最佳尺寸。 (C)2015 Elsevier B.V.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号