A 3-D nonlinear thermal circuit model of underground MV power cables and their joints

机译:地下中压电力电缆及其接头的3D非线性热回路模型

获取原文
获取原文并翻译 | 示例
           

摘要

A 3D thermal model of underground power cable is presented in this paper. A detailed representation of the cable and its joints, the laying condition, the soil and the heat exchanges between soil upper surface and air, considering different weather conditions, is given. The model solves the thermal problem by means of an equivalent electric circuit and has been validated against field measurements, showing its applicability both for steady state and transient studies.In order to verify if any correlation between the occurrence of overheatings and the anomalous increase of failures, observed by Italian Distribution System Operators (DSOs) during summer 2015, exists, the model has been applied to simulate one-year operation of an existing underground cable. The cable is located in the MV distribution network owned by A.S.M. Temi S.p.A., the DSO in Terni, a city placed in the Central Italy. Ambient temperature and relative humidity trends have been taken from registrations made by a weather station, whereas the current profile along the cable has been assumed equal to that measured in 2015 by A.S.M., sampled every ten minutes. A second current profile has been also used, derived from the measured one in order to have the cable loaded at ampacity for a considerable time span during the year. In all cases, results show that no overheating occurred and, moreover, that the joint is the coldest part of the underground power cable.
机译:本文提出了地下电缆的3D热模型。考虑到不同的天气条件,给出了电缆及其接头,铺设条件,土壤以及土壤上表面与空气之间的热交换的详细表示。该模型通过等效电路解决了热问题,并已通过现场测量验证,显示了其在稳态和瞬态研究中的适用性。为了验证过热的发生与故障异常增加之间是否存在任何相关性由意大利配电系统运营商(DSO)于2015年夏季观察到,该模型已应用于模拟现有地下电缆的一年运行情况。该电缆位于A.S.M.拥有的MV配电网络中。 Temi S.p.A.,位于意大利中部城市特尔尼(Terni)的DSO。环境温度和相对湿度趋势是从气象站进行的记录中得出的,而沿电缆的当前剖面被假定为等于A.S.M.在2015年测量的剖面,每十分钟采样一次。还使用了第二个电流分布图,该电流分布图是从测得的电流分布图中得出的,以便在一年中的相当长的时间跨度内将电缆载于载流量。在所有情况下,结果均表明未发生过热现象,而且接头是地下电缆的最冷部分。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号