摘要

The paper describes a technique for simulating the presence of partial discharges in gas-insulated substation (GIS) equipment. The technique employs a pulse generator to inject current pulses through a suitable protrusion. The current pulses have similar temporal characteristics to those produced by an actual discharge event, with the added advantage that their magnitudes can be controlled accurately. Because the pulses are highly reproducible, they are ideally suited for investigating the UHF technique of partial discharge detection. The paper discusses the relationship between the magnitude of the UHF signal received by a coupler and the discharge magnitude. It also shows that the coupler signal is dependent on the protrusion length and on the spatial relationship between the protrusion and the coupler. The implications for practical discharge measurements in GIS also are discussed.
机译:本文介绍了一种模拟气体绝缘变电站(GIS)设备中局部放电的技术。该技术采用脉冲发生器通过合适的突起注入电流脉冲。电流脉冲具有与实际放电事件所产生的时间特性相似的时间特性,其附加优点是可以精确控制其幅度。由于脉冲具有很高的重现性,因此非常适合研究局部放电检测的UHF技术。本文讨论了耦合器接收的UHF信号的大小与放电大小之间的关系。它还表明耦合器信号取决于突起的长度以及突起和耦合器之间的空间关系。还讨论了GIS中实际流量测量的含义。