A transmission tower model that can reproduce the lightning surge response is important for analyzing the lightning surge. In developing such tower model, however, studies have been conducted using a stand-alone tower or a condition where the tower and transmission lines are orthogonally crossed. This could be attributable to the difficulty in handling a complex layout in conventional experiments and theoretical studies. The present paper verifies the accuracy of the FDTD analysis, based on a comparison with the experimental results. Subsequently, it studies the influence of the layout and the inclined angle of the incoming lines to the substation on the surge response of the tower under near-real facility conditions via electromagnetic field analysis using the FDTD method. As a result, the voltage of the insulator strings peaked with a zero-degree incoming angle and it declined with increasing angle, namely by about 20% when the inclined angle was 37.5 degrees. Finally, the current waveform was analyzed in addition to the voltage characteristics and the generation mechanism of the line voltage was explained.
机译:可以再现雷电冲击响应的输电塔模型对于分析雷电冲击很重要。然而,在开发这样的塔架模型中,已经使用独立塔架或塔架和传输线正交交叉的条件进行了研究。这可能归因于在常规实验和理论研究中难以处理复杂的布局。在与实验结果进行比较的基础上,本文验证了FDTD分析的准确性。随后,通过使用FDTD方法的电磁场分析,研究了近实际设施条件下输电线路的布局和到变电站的倾斜角​​度对塔架喘振响应的影响。结果,绝缘子串的电压以零度入射角达到峰值,并随角增加而下降,即当倾斜角为37.5度时下降约20%。最后,除了分析电压特性外,还分析了电流波形,并说明了线电压的产生机理。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号