首页> 外文期刊>E3S Web of Conferences >Calculation of 220kV Transformer Bias Current Based on the Earth and Power Grid Model in the Metro Area
【24h】

Calculation of 220kV Transformer Bias Current Based on the Earth and Power Grid Model in the Metro Area

机译:基于地球电网模型的220kV变压器偏置电流计算

获取原文
           

摘要

The metro stray current will be generated during subway operation, which will affect the electromagnetic environment near the subway, and then affect the surrounding 220kV transformer. In order to analyze the influence of stray current on the DC bias of the transformer, this paper calculates the magnitude of the stray current through the resistance network model, and then analyzes the changes in the surrounding ground potential caused by the stray current based on the earth resistivity model. Finally, the 220kV transformer network topology model of the city network was established, and the relationship between the neutral point current of the transformer and time was obtained. It provided a quantitative method for research the correlation between subway stray current and 220kV transformer bias current phenomenon and calculate the bias current of 220kV transformer in urban network near subway.
机译:在地铁操作期间将产生地铁流动电流,这将影响地铁附近的电磁环境,然后影响周围的220kV变压器。 为了分析杂散电流对变压器直流偏置的影响,本文通过电阻网络模型计算杂散电流的大小,然后分析基于杂散电流引起的周围地面电位的变化 地球电阻率模型。 最后,建立了城市网络的220kV变压器网络拓扑模型,获得了变压器的中性点电流与时间的关系。 它提供了研究地铁杂散电流和220kV变压器偏置电流现象之间的相关性的定量方法,并在地铁附近城市网络中的220kV变压器偏置电流。