Improvement of 33kv Overcurrent Protection Scheme for Effurun Transmission Substation at PTI Road, Delta State, Nigeria

机译:尼日利亚Pti Road,Delta State,Delta State,Delta State,Delta State,Delta State的改进

获取原文
           

摘要

The research work is initiated to investigate Effurun 3x 60MVA, 132/33kV transmission substationnetwork, because this network faced fire outbreak, power outage several times, and abnormal tripping of feederduring last couple of years. Using ETAP software as analytical tool, the network was drawn. The data for eachcomponent in the network was collected from a site visit. The simulator was ruined and different fault scenarioswere created to analyse the existing overcurrent protection schemes and different miss-coordination oroperations results were obtained as a response of protection system to the abnormal conditions. Afterstudying this network, it was noticed that one of the main reasons for fire outbreak, outage of power andabnormal tripping of protection devices is the relay setting miss-coordination caused by the use of only definiteminimum time (DMT) and grading by time overcurrent protection scheme. Inverse definite minimum time(IDMT)relay and grading by both Time current overcurrent protection scheme was chosen, and this scheme is modelledwhich starts first by coordinating three phase overcurrent elements, for different paths from furthestdownstream up to the upstream. Next the instantaneous element as a backup protection as appliedsuccessfully. The new relay setting coordination has been applied to all relays in the Effurun substation as aresult from this study. The sequence of operation is well improved and total outage of power, abnormaltripping of feeders is significantly reduced.
机译:启动研究工作是为了调查Effulun3 X 60MVA,132 / 33kV传输变电站,因为这个网络面临着消防爆发,停电几次,并且过去几年的饲料跳闸异常绊倒。使用ETAP软件作为分析工具,绘制了网络。从网站访问中收集了网络中的每款Component的数据。模拟器被破坏了,并创建了不同的故障场景,以分析现有的过电流保护方案,并获得不同的错过协调替换结果作为保护系统对异常情况的响应。上方的网络,有人注意到消防爆发的主要原因之一,防护装置的电力跳闸的中断是通过仅使用默认的时间(DMT)和随时间过流保护方案进行分级引起的继电器设置错失协调。选择逆明确的最小时间(IDMT)继电器通过两个时间过电流保护方案进行转换和分级,并且该方案通过协调三相过电流元素首先开始,对于从FurthestDownstream到上游的不同路径,首先开始。接下来,瞬时元素作为备份保护,如应用才能。新的继电器设定协调已经应用于Effulun变电站中的所有继电器作为本研究的遗产。操作顺序得到良好的改善和功率的总阻碍,饲养剂的异常显着降低。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号