In recent years, the external thermal insulation system (ETIS) has been applied increasingly in a large amount of buildings for energy conservation purpose. However, the increase use of combustible insulation materials in the ETIS has raised serious fire safety problems. Fires involving this type of ETIS have caused severe damage and loss. In order to improve its fire safety, fire barriers were suggested to be installed.This paper introduces fire experiments that have been done to study the effects of fire barriers on preventing vertical fire spread along the ETIS. The experiments were performed according to BS 8414-1:2002 “Fire performance of external cladding systems – Part 1: Test method for non-loadbearing external cladding systems applied to the face of the building”. The test facility consists of a 9 m high wall. The fire sources were wood cribs with a fire size of 3 ± 0.5 MW. The insulation materials were expanded polystyrene foam (EPS). The fire barrier was a horizontal strip of rockwool with a width of 300 mm. Thermocouples were used to measure temperatures outside and inside the ETIS.A series of experiments with different fire scenarios were done: no fire barrier, two fire barriers and three fire barriers at different heights. Test results were compared. The results show that the ETIS using EPS without fire barriers almost burned out, while the ETIS with fire barriers performed well in preventing fire spread. The temperatures above the fire barrier were much lower than those below the fire barrier, and most of the insulation materials above the top fire barrier stayed in place.
机译:近年来,外部保温系统(ETIS)越来越多地用于节能建筑中。但是,在ETIS中越来越多地使用可燃绝缘材料引起了严重的消防安全问题。涉及此类ETIS的火灾已造成严重的破坏和损失。为了提高其防火安全性,建议安装防火屏障。本文介绍了进行防火实验,以研究防火屏障对防止垂直火势沿ETIS扩散的影响。根据BS 8414-1:2002“外部砌面系统的防火性能–第1部分:应用于建筑物表面的非承重外部砌面系统的测试方法”进行了实验。测试设备由9微米高的墙组成。火源是木床,火势为3±0.5 MW。绝缘材料是膨胀的聚苯乙烯泡沫(EPS)。防火壁是一块水平的岩棉带,宽度为300 stripmm。使用热电偶测量ETIS外部和内部的温度。进行了一系列针对不同火灾情况的实验:无防火屏障,两个防火屏障和三个不同高度的防火屏障。比较测试结果。结果表明,使用EPS的无防火障碍物的ETIS几乎被烧毁,而带有防火障碍物的ETIS在防止火灾蔓延方面表现良好。防火壁上方的温度远低于防火壁下方的温度,顶部防火壁上方的绝大部分保温材料都留在原位。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号