首页> 外文期刊>E3S Web of Conferences >Influence of installation of displacement ventilation diffusers above occupied zone on the vertical temperature gradient in simulated office rooms
【24h】

Influence of installation of displacement ventilation diffusers above occupied zone on the vertical temperature gradient in simulated office rooms

机译:在居住区上方安装置换通风扩散器对模拟办公室室内垂直温度梯度的影响

获取原文
           

摘要

Displacement ventilation diffusers are typically installed to the occupied zone, which can limit the utilization of the displacement ventilation. This paper presents the full-scale test results of two simulated office rooms with installation of displacement diffusers near wall, above the occupied zone. Vertical temperature gradients are compared to full-scale tests with installation of displacement diffusers to the occupied zone. The full-scale test setup consisted of two displacement diffusers and ceiling exhaust in wellinsulated room with 20.7 m2 floor area and room heights of 5.1 m and 3.3 m. The internal heat loads simulated situations with 10 occupants (simulated with heated cylinders), fluorescent lighting units, solar load on window surface (heated foils in one wall) without/with direct solar load on floor (heated foil on floor). The installation of displacement ventilation diffusers above occupied zone influenced on the vertical temperature gradient above the occupied zone only slightly. It reduced the vertical temperature gradient in the occupied zone. This confirms the operation of the displacement ventilation with this installation. This can be advantageous due to the smaller temperature stratification in the occupied zone, still the ventilation efficiency can be slightly lower comparing to the typical installation of the displacement diffusers.
机译:置换通风扩散器通常安装在占用区域,这会限制置换通风的利用。本文介绍了两个模拟办公室的完整测试结果,这些办公室在靠近被占领区域的墙壁附近安装了位移扩散器。将垂直温度梯度与将位移扩散器安装到占用区域的全面测试进行比较。全面测试装置由两个排量扩散器和天花板排气组成,该房间在隔热良好的房间中,占地面积为20.7 m2,房间高度为5.1 m和3.3 m。内部热负荷模拟情况下有10名乘员(用加热的钢瓶模拟),荧光灯照明装置,窗户表面的太阳负荷(一面墙中的加热箔),而没有/在地板上有直接的太阳负荷(地板上的加热箔)。占用区上方的位移通风扩散器的安装仅对占用区上方的垂直温度梯度产生轻微影响。它降低了所占区域的垂直温度梯度。这确认了此装置的置换通风的操作。由于在占用区域中较小的温度分层,因此这可能是有利的,但是与排量扩散器的典型安装相比,通风效率仍然会略低。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号