首页> 外文期刊>IFAC PapersOnLine >A Coordinated LVRT Control for a PMSG Wind Turbine
【24h】

A Coordinated LVRT Control for a PMSG Wind Turbine

机译:PMSG风机的LVRT协调控制

获取原文
           

摘要

This paper proposes a coordinated controller for a permanent-magnet synchronous generator wind turbine to enhance its low voltage ride through capability. In the proposed method, both rotor side and grid side converters are cooperatively controlled to regulate the DC link voltage during the grid fault. Moreover, at the fault clearance, the grid side converter produces the previous power value which is the maximum power in normal operation. It prevents excessive power production at the fault clearance in order to reduce the rotor load. From the proposed method, better transient response of the DC link voltage could be obtained with less rotor acceleration. We validated the proposed method using MATLAB/Simulink SimPowerSystems and compared the performances of with and without the coordinated control.
机译:本文提出了一种永磁同步发电机风力发电机的协调控制器,以提高其低压穿越能力。在所提出的方法中,在电网故障期间,转子侧转换器和电网侧转换器都被协同控制以调节直流母线电压。此外,在故障清除时,电网侧转换器会产生先前的功率值,该功率值是正常运行中的最大功率。它可以防止在故障间隙产生过多的功率,从而减少转子负载。从提出的方法中,可以以较小的转子加速度获得更好的直流母线电压瞬态响应。我们使用MATLAB / Simulink SimPowerSystems验证了所提出的方法,并比较了使用和不使用协调控制的性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号