Seismic performance of emergency diesel generator for high frequency motions

机译:应急柴油发电机高频运动的抗震性能

获取原文
           

摘要

The nuclear power plants in South Korea have been designed in accordance with the U.S. Regulatory Guide 1.60 (R.G 1.60) design spectrum of which the peak frequency range is 2–10?Hz. The characteristics of the earthquakes at the Korea nuclear power plant sites were observed to be closer to that of Central and Eastern United States (CEUS) than the R.G 1.60, which is a lower amplification in a low frequency range, and a higher amplification in a high frequency range. The possibility of failure for sensitive power plant components in the high frequency range has been considered and evaluated. In this study, in order to improve the reliability of nuclear plant and administrative control procedures, seismic tests of an emergency diesel generator (EDG) were conducted using a shaking table under both high and low frequency ranges. From the tests, oil/lubricant leaks from the bolt connections, the fuel filter and the fuel inlet were observed. Therefore, the check list of nuclear plant components after an earthquake should include bolt connections of EDG as well as anchor bolts.
机译:韩国的核电厂是根据美国监管指南1.60(R.G 1.60)设计频谱进行设计的,该频谱的峰值频率范围为2-10?Hz。与RG 1.60相比,韩国核电站现场的地震特征比RG 1.60更接近中部和东部(CEUS),后者在低频范围内放大率较低,而在RG-1范围内放大率较高。高频范围。已经考虑并评估了高频范围内敏感电厂组件发生故障的可能性。在这项研究中,为了提高核电厂的可靠性和行政控制程序,使用振动台在高频和低频范围内对应急柴油发电机(EDG)进行了地震测试。通过测试,观察到螺栓连接,燃油滤清器和燃油进口处的机油/润滑油泄漏。因此,地震后核电站部件检查清单应包括EDG的螺栓连接以及地脚螺栓。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号