首页> 外文期刊>Frontiers in Heat Pipes >AXIAL TEMPERATURE DISTRIBUTION AND PERFORMANCE OF R410A AND WATER FILLED THERMOSYPHON AT VARIOUS FILL RATIOS AND INCLINATIONS
【24h】

AXIAL TEMPERATURE DISTRIBUTION AND PERFORMANCE OF R410A AND WATER FILLED THERMOSYPHON AT VARIOUS FILL RATIOS AND INCLINATIONS

机译:R410A和充水热电偶在各种填充比和倾角下的轴向温度分布和性能

获取原文
           

摘要

Axial wall temperature distribution of R410a and water filled thermosyphons at various fill ratios and inclination angles are experimentally determined. Power was supplied using resistance band heaters. A water cooled jacket surrounded the condenser section. Power input ranged from 100 – 830 W. Fill ratios of 0.93, 0.66, 0.4 and 0.25 were employed for the R410a pipe and 1.00, 0.75, 0.50 and 0.25 for the water filled pipe. Inclination angles were set at 30o, 50o, 70o and 90o. The results showed that the evaporator wall temperature was not uniform especially at high power input, low fill ratios and large inclinations.
机译:通过实验确定了R410a和充满水的热虹吸管在各种填充比和倾角下的轴向壁温度分布。使用电阻带加热器供电。水冷套包围冷凝器部分。输入功率范围为100 – 830W。R410a管道的填充比为0.93、0.66、0.4和0.25,注水管道的填充比为1.00、0.75、0.50和0.25。倾斜角度设置为30o,50o,70o和90o。结果表明,蒸发器壁温不均匀,特别是在高功率输入,低填充率和大倾角的情况下。

著录项