首页> 外文期刊>Engineering journal >Performance Study on a Window Type Air Conditioner Condenser Using Alternative Refrigerant R407C
【24h】

Performance Study on a Window Type Air Conditioner Condenser Using Alternative Refrigerant R407C

机译:窗式空调冷凝器R407C替代制冷剂的性能研究

获取原文
           

摘要

In this work, a performance study was achieved on air cooled condenser of an air-conditioning unit. An experimental investigation was carried out on two condenser designs aided by a controlled environmental zone, which was designed and constructed for the current study. The effect of ambient air temperature on the condenser performance was studied by varying the controlled zone air temperature from 30 to 50oC. The first design is a four circuits 5/16" tube diameter condenser and the second is an eight circuits design with the same diameter. The experimental results showed that, an increase in the ambient air temperature has a negative effect on COP due to the decrease in the overall heat rejected, yet has a positive effect on refrigerant side pressure drop.
机译:在这项工作中,对空调单元的风冷冷凝器进行了性能研究。在可控环境区域的辅助下,对两种冷凝器设计进行了实验研究,这是针对当前研究而设计和建造的。通过将受控区域的空气温度从30oC改变为50oC,研究了环境空气温度对冷凝器性能的影响。第一种设计是直径为5/16英寸的四回路冷凝器,第二种是直径相同的八回路设计。实验结果表明,环境空气温度的升高会降低COP对COP产生负面影响在排出的总热量中,对制冷剂侧压降有积极影响。