首页> 外文期刊>International Journal of Physical Sciences >Optimization of the louver angle and louver pitch for a louver finned and tube heat exchanger
【24h】

Optimization of the louver angle and louver pitch for a louver finned and tube heat exchanger

机译:百叶窗翅片管换热器的百叶窗角度和百叶窗间距的优化

获取原文
           

摘要

The optimization of the louver angle (θ) and the louver pitch (Lp) for a louver finned and tube heat exchanger was investigated numerically along with a simplified conjugate-gradient method (SCGM). The area reduction ratio relative to a plain surface is the objective function to be maximized. A search for the optimum louver angle (θ) and louver pitch (Lp), ranging from 15°& θ & 40° and 2 mm & Lp & 3.2 mm, respectively, was performed. The results showed that the maximum area reduction ratios may reach 39~46% combined with the optimal design of (θ, Lp) at ReD= 589~3533 (Uin= 0.5-3.0 m/s).
机译:百叶窗翅片管换热器的百叶窗角度(θ)和百叶窗间距(Lp)的优化与简化的共轭梯度法(SCGM)一起进行了数值研究。相对于平面的面积减小率是要最大化的目标函数。搜索最佳百叶窗角度(θ)和百叶窗间距(Lp),其范围为15°≤θ。 θ & 40度和2毫米& Lp <分别进行3.2mm。结果表明,在ReD = 589〜3533(Uin = 0.5-3.0 m / s)的情况下,结合(θ,Lp)的最佳设计,最大面积减小率可以达到39〜46%。