首页> 外文期刊>Cadernos de Saúde Pública >Work accidents and automatic circuit reclosers in the electricity sector: beyond the immediate causesAccidentes de trabajo y reconectadores automáticos en el sector eléctrico: más allá de las causas inmediatas
【24h】

Work accidents and automatic circuit reclosers in the electricity sector: beyond the immediate causesAccidentes de trabajo y reconectadores automáticos en el sector eléctrico: más allá de las causas inmediatas

机译:电力部门的工作事故和自动重合闸:超出直接原因电力部门的工作事故和自动重合闸:超出直接原因

获取原文
           

摘要

The Brazilian electricity sector has recorded high work-related mortality rates that have been associated with outsourcing, used to cut costs. In order to decrease the power outage time for consumers, the industry adopted the automatic circuit recloser as the technical solution. The device has hazardous implications for maintenance workers. The aim of this study was to analyze the origins and consequences of work accidents in power systems with automatic circuit recloser, using the Accident Analysis and Prevention (AAP) model. The AAP model was used to investigate two work accidents, aimed to explore the events’ organizational origins. Case 1 - when changing a deenergized secondary line, a worker received a shock from the energized primary cable (13.8kV). The system reclosed three times, causing severe injury to the worker (amputation of a lower limb). Case 2 - a fatal work accident occurred during installation of a new crosshead on a partially insulated energized line. The tip of a metal cross arm section strap touched the energized secondary line and electrocuted the maintenance operator. The circuit breaker component of the automatic circuit recloser failed. The analyses revealed how business management logic can participate in the root causes of work accidents through failures in maintenance management, outsourced workforce management, and especially safety management in systems with reclosers. Decisions to adopt automation to guarantee power distribution should not overlook the risks to workers in overhead power lines or fail to acknowledge the importance of ensuring safe conditions.
机译:巴西电力部门记录了与外包相关的高工作相关死亡率,用于降低成本。为了减少用户的停电时间,业界采用了自动电路重合器作为技术解决方案。该设备对维护人员有危害。这项研究的目的是使用事故分析和预防(AAP)模型来分析具有自动电路重合闸的电力系统中工作事故的起因和后果。 AAP模型用于调查两次工伤事故,旨在探究事件的组织根源。情况1-更换断电的二次线时,工人从通电的主电缆(13.8kV)中受到电击。该系统关闭了3次,对工人造成了严重伤害(下肢截肢)。案例2-在部分绝缘的通电线路上安装新的十字头时发生致命的工作事故。金属横臂截面皮带的尖端触及通电的二次管线,并电击了维修操作员。自动重合闸的断路器组件发生故障。分析揭示了业务管理逻辑如何通过维护管理,外包的劳动力管理,尤其是带有重合闸的系统中的安全管理中的故障,来参与工作事故的根本原因。采用自动化来保证配电的决策不应忽略架空输电线对工人的风险,也不应忽视确保安全条件的重要性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号